Singh, Bhim ; Bhuvaneswari, G. ; Garg, Vipin (2006) 24-pulse AC-DC converter for power quality improvement in vector controlled induction motor drives Electric Power Components and Systems, 34 (10). pp. 1077-1098. ISSN 1532-5008
Full text not available from this repository.
Official URL: http://www.tandfonline.com/doi/full/10.1080/153250...
Related URL: http://dx.doi.org/10.1080/15325000600630335
Abstract
This article deals with autotransformer based multipulse AC-DC converters feeding vector controlled induction motor drives (VCIMDs) for improving power quality at the point of common coupling (PCC). The proposed 24-pulse AC-DC converter is realized on the principle of DC ripple re-injection technique for pulse multiplication and harmonic mitigation. The design of the autotransformer is given for the proposed AC-DC converter for making it suitable for retrofit applications, where presently a 6-pulse diode bridge rectifier is used. The effect of load variation on VCIMD is also studied to demonstrate the effectiveness of the proposed AC-DC converter. The test results, along with simulated results, on a developed laboratory prototype are presented to validate the design and model of the proposed 24-pulse AC-DC converter.
Item Type: | Article |
---|---|
Source: | Copyright of this article belongs to Taylor and Francis Group. |
Keywords: | Autotransformer; Multipulse AC-DC Converter; Pulse Multiplication; Power Quality; VCIMD |
ID Code: | 106700 |
Deposited On: | 07 Aug 2017 12:15 |
Last Modified: | 07 Aug 2017 12:15 |
Repository Staff Only: item control page