Symmetrical components-based modified technique for power-quality disturbances detection and classification

Kumar, Raj ; Singh, Bhim ; Shahani, D. T. (2016) Symmetrical components-based modified technique for power-quality disturbances detection and classification IEEE Transactions on Industry Applications, 52 (4). pp. 3443-3450. ISSN 0093-9994

Full text not available from this repository.

Official URL: http://ieeexplore.ieee.org/document/7422742/

Related URL: http://dx.doi.org/10.1109/TIA.2016.2536665

Abstract

This paper presents a modified approach based on symmetrical components in time domain for the detection and classification of various power-quality (PQ) disturbances. Single-phase PQ disturbance signal along with the two other ideal phases generated using phase-locked loop (PLL) is processed to find out the symmetrical components of all phases in time domain. Triggering points for PQ disturbances have been detected from the negative-sequence component of disturbance phase and have been easily classified from the signatures of the waveforms using the summation of the positive- and negative-sequence components. PQ disturbances, such as voltage sag, swell, interruption, harmonics, flicker, transients, notches, and spike present in a distribution system, have been investigated and are easily localized and segmented with this technique. Being a time-domain technique, it can be adopted for the online monitoring and assessment of the PQ disturbances. Simulated and real-time results are presented for a number of PQ disturbances to show the effectiveness of the proposed method for the PQ disturbances detection and classification.

Item Type:Article
Source:Copyright of this article belongs to Institute of Electrical and Electronics Engineers.
Keywords:Disturbance; Power Quality (PQ); Symmetrical Components; Transform; Wavelet
ID Code:106429
Deposited On:07 Aug 2017 12:36
Last Modified:07 Aug 2017 12:36

Repository Staff Only: item control page