Battery energy storage system based controller for a wind turbine driven isolated asynchronous generator

Singh, Bhim ; Kasal, Gaurav Kumar (2008) Battery energy storage system based controller for a wind turbine driven isolated asynchronous generator Journal of Power Electronics, 8 (1). pp. 81-90. ISSN 1598-2092

[img]
Preview
PDF - Other
356kB

Official URL: http://www.jpe.or.kr/archives/view_articles.asp?se...

Abstract

This paper presents an investigation of a voltage and frequency controller for an isolated asynchronous generator (IAG) driven by a wind turbine and supplying 3-phase 4-wire loads to the isolated areas where a grid is not accessible. The control strategy is based on the indirect current control of the VSC (voltage source converter) using the frequency PI controller. The proposed controller consists of three single-phase IGBT (Insulated Gate Bipolar Junction Transistor) based VSC, which are connected to each phase of the IAG through three single phase transformers and a battery at their DC link. The controller has the capability of controlling reactive and active powers to regulate the magnitude and frequency of the generated voltage, harmonic elimination, load balancing and neutral current compensation. The proposed isolated system is modeled and simulated in MATLAB using Simulink and PSB (Power System Block-set) toolboxes to verify the performance of the controller.

Item Type:Article
Source:Copyright of this article belongs to Korean Institute of Power Electronics.
Keywords:Isolated Asynchronous Generator; Wind Turbine; Voltage and Frequency Controller; 3-Phase 4-Wire System
ID Code:106544
Deposited On:07 Aug 2017 13:19
Last Modified:07 Aug 2017 13:19

Repository Staff Only: item control page